| 1 | Continuous current rating | Select an ATS with a continuous current rating of at least 800 A at the actual system voltage, frequency, ambient temperature, enclosure type, and installation conditions. Do not treat the frame size alone as the usable rating. | Confirm the rated operational current, rated insulation voltage, temperature-rise limits, conductor arrangement, and any derating requirements. The upstream and downstream protection must also be coordinated with the 800 A rating. |
| 2 | Switching mechanism | Compare mechanically held and electrically held mechanisms. Mechanically held designs generally maintain contact position without continuous coil power, while electrically held designs may require continuous control power to remain in position. | Check the mechanism type, motor or solenoid duty cycle, manual operating method, emergency operation, mechanical interlocking, and the number of operations covered by the endurance rating. |
| 3 | Open, closed, or delayed transition | Use open transition when the sources must never be paralleled. Consider closed transition only when the utility, generator, protection system, and local regulations permit momentary source paralleling. Use delayed transition where residual voltage decay or motor load characteristics require a controlled neutral position. | Verify the transition sequence, source interlocks, synchronization requirements, adjustable neutral delay, in-phase monitoring, and whether the design prevents unintended paralleling. |
| 4 | Transfer and retransfer performance | Evaluate sensing-to-transfer behavior rather than relying on a single advertised transfer-time figure. Transfer time depends on source qualification, engine-start delay, contactor or breaker movement, control settings, and load conditions. | Confirm adjustable undervoltage and underfrequency pickup thresholds, time delays, engine-start contacts, source-available logic, retransfer delay, and measured switching time under representative conditions. |
| 5 | Short-circuit withstand and closing performance | Match the ATS short-circuit withstand and closing rating to the available fault current at the installation point. An 800 A continuous rating does not by itself define the fault-current capability. | Review the tested short-circuit current rating or conditional short-circuit rating, test duration, protective-device requirements, system voltage, and whether the rating applies to the complete ATS assembly. |
| 6 | Phase, neutral, and sensing configuration | Select the correct system configuration: three-phase or single-phase, three-pole or four-pole switching, solid or switched neutral, and the required voltage-sensing arrangement. A switched neutral may be necessary where separately derived sources require isolation of the neutral conductor. | Confirm pole configuration, neutral ampacity, phase-loss and phase-sequence detection, voltage and frequency sensing range, generator warm-up logic, and compatibility with the grounding and bonding design. |
| 7 | Standards, maintenance, and monitoring | Choose equipment evaluated to the applicable requirements, such as UL 1008 or IEC 60947-6-1, and provide clear access for inspection, testing, and service. For critical loads, include remote status and event indication. | Verify certification for the intended market, routine test procedures, inspection intervals, replaceable control components, auxiliary contacts, alarm outputs, communication options, maintenance bypass provisions, and documented factory test results. |