| 1 | Rated Voltage and Insulation Level | Match the breaker rated voltage, power-frequency withstand voltage, and lightning impulse withstand voltage with the system and switchgear insulation levels. | Common medium-voltage classes include 12 kV, 17.5 kV, 24 kV, and 36 kV. Values vary by network and standard. | Utility distribution substations, industrial distribution boards, and renewable-energy collector systems. | Confirm the highest system voltage and local insulation-coordination requirements before selecting the model. |
| 2 | Continuous Current Rating | Check the continuous current rating, temperature-rise limits, conductor size, and enclosure ventilation under the actual installation conditions. | Ratings such as 630 A, 1250 A, 2000 A, and 3150 A are commonly encountered in medium-voltage equipment. | Incoming feeders, bus-section couplers, transformer feeders, and high-load industrial circuits. | Select a rating based on continuous load, future expansion, ambient temperature, altitude, and derating requirements. |
| 3 | Short-Circuit Breaking Capacity | Compare the rated short-circuit breaking current and short-time withstand current with the calculated prospective fault current at the installation point. | Common medium-voltage short-circuit ratings include approximately 16 kA, 25 kA, and 31.5 kA; higher ratings are also available. | High-capacity substations, large industrial plants, data centers, and power-generation facilities. | Use an up-to-date fault study and allow for changes in transformer capacity or distributed generation. |
| 4 | Standards and Type-Test Evidence | Request test documentation covering dielectric performance, temperature rise, short-circuit operations, mechanical endurance, and internal arc requirements where applicable. | IEC 62271-100 is widely used for high-voltage AC circuit breakers; IEEE C37.04 and IEEE C37.09 are commonly used in North American projects. | Export projects, regulated utilities, industrial plants, and safety-critical facilities. | Verify that certificates apply to the proposed design, voltage class, current rating, and tested configuration. |
| 5 | Operating Mechanism and Duty Cycle | Review the stored-energy mechanism, opening and closing times, rated operating sequence, electrical endurance, and mechanical endurance. | Medium-voltage vacuum breakers commonly use spring-operated mechanisms and may support sequences such as O–0.3 s–CO–15 s–CO, subject to the specific design. | Automatic feeder protection, bus transfer, motor control, and frequent switching installations. | Match the duty cycle to the protection scheme and switching frequency rather than selecting only by current rating. |
| 6 | Vacuum Interrupter Performance | Evaluate contact material, contact erosion indication, interrupter withstand capability, rated interruption current, and expected service life. | Vacuum interrupters are widely used for medium-voltage switching because the vacuum provides high dielectric recovery and requires no oil or insulating gas for interruption. | General feeder protection, transformer switching, motor switching, and capacitor-bank switching with suitable application controls. | Ask for contact-wear limits and replacement or inspection procedures, especially for high-operation applications. |
| 7 | Application-Specific Switching Duty | Check whether the breaker is suitable for transformer, motor, capacitor-bank, reactor, or cable switching and whether surge-control measures are required. | Vacuum switching can produce steep voltage transients in some motor and transformer applications; surge arresters, controlled switching, or suitable cable arrangements may be needed. | Medium-voltage motors, transformers, capacitor banks, shunt reactors, and long cable feeders. | Provide the load type, motor size, transformer impedance, cable length, and switching frequency during technical review. |
| 8 | Protection, Control, and Interlocking | Confirm trip and close-coil voltages, auxiliary contacts, anti-pumping functionality, electrical and mechanical interlocks, protection-relay compatibility, and communication interfaces. | Common control supplies include 24 V, 48 V, 110 V, 125 V, and 220 V DC, but the required value depends on the project control system. | Substation automation, remote feeder operation, backup protection, and automatic transfer systems. | Prepare a complete control schematic and point list before placing the purchase order. |
| 9 | Installation Environment and Enclosure | Review indoor or outdoor installation, altitude, ambient temperature, humidity, dust, corrosion, seismic conditions, ingress protection, and internal arc classification. | Standard ratings are often based on defined ambient and altitude conditions; correction factors may be required above 1000 m or in severe environments. | Indoor metal-enclosed switchgear, outdoor substations, coastal plants, mines, and high-altitude installations. | State site conditions clearly and verify enclosure, ventilation, heater, coating, and altitude requirements. |
| 10 | Lifecycle Cost and Service Support | Compare purchase price, commissioning, spare parts, inspection intervals, operating mechanism maintenance, training, documentation, and expected availability. | Vacuum interrupters generally require less routine medium replenishment than oil circuit breakers, but mechanism, control, insulation, and contact condition still require inspection. | Remote substations, continuous-process plants, hospitals, data centers, and facilities with high outage costs. | Evaluate total cost of ownership and require manuals, drawings, test reports, spare-parts lists, and commissioning support. |